Infrared Thermography

Infrared thermography surveys for electrical and mechanical plant

Non-invasive thermal imaging of electrical distribution and mechanical equipment under normal operating load, with findings graded by temperature rise and criticality.

Close-up of gas turbine compressor blades inside a power plant casing

A loose or corroded electrical connection heats up long before it fails. Infrared thermography finds those connections while the plant is running, without opening a process or taking a shutdown, and gives a maintenance team the evidence to correct them at the next planned window instead of after an outage.

Surveys are conducted with a radiometric camera, with the equipment carrying a representative load — a survey taken at low load will understate a fault or miss it entirely. Emissivity and reflected temperature are set for each target, and every anomaly is recorded with a thermal image, a visible-light reference image, the measured delta against a reference phase or similar component, and the load at the time of measurement.

Findings are graded by temperature rise and by what the component feeds, so an 8 °C delta on a critical incomer is not buried beneath a 30 °C delta on a redundant lighting circuit. Anything judged an imminent failure risk is raised verbally before leaving site.

Conditions commonly identified

  • Loose, corroded or under-torqued electrical connections
  • Phase imbalance and overloaded circuits
  • Failing contactors, breakers, fuses and isolators
  • Transformer cooling and winding temperature anomalies
  • Overheating bearings, couplings and drive belts
  • Failed steam traps and blocked heat exchanger passes
  • Refractory, insulation and building envelope losses

What you receive

  • Thermal image paired with a visible-light reference for every anomaly
  • Measured delta against reference phase or comparable component
  • Load conditions recorded at the time of measurement
  • Severity classification with a recommended timescale for correction
  • Verbal notification on site for imminent failure risks
  • Retest recommendation to confirm the repair after correction

Infrared Thermography — common questions

Do panels need to be opened for a thermal survey?

For electrical surveys, yes — infrared cannot see through a metal cover. Panel opening is carried out under your permit system by a competent person, or we can work to installed IR viewing windows where you have them.

What load does the plant need to be under?

As close to normal operating load as possible, and ideally at least 40% of rated. A survey at low load understates temperature rise and can miss a developing fault entirely. Load at the time of measurement is recorded against every finding.

How often should an electrical thermal survey be done?

Annually is the common interval for main distribution and MCCs, and many insurers ask for it. Six-monthly is worth considering on critical or heavily cycled switchgear.